Menu INPUTS
2.3 Diameter Menu
Diameter calibration
With an analog diameter measure, the signal must be calibrated from physical values (upper point
= max diameter, lower point = min diameter).
Valid max diameter: Type in the max diameter value.
Valid min diameter: Type in the min diameter value.
The diameter unit is chosen in the DISPLAY menu.
Procedure: Fill the values and click on memory used, then physically simulate the max diameter
and click on the button "valid max diameter," wait 5 seconds and do the same with min
diameter and the button "valid min diameter."